6. System Faults

Fault Condition Result Reset

|

LMU Comm Break

|

Slave to slave connection break. [ GUI ] : GUI will show LMU Comm Break fault.

[ System ] : All contactors open.
[ Auto Reset ] : When connection is rectified, error will be reset after hard reset.

[ Manual Reset ] : Rectify the connection and do hard reset.

|

IMD Fault

|

Insulation break between battery positive, battery negative and chassis. [ GUI ] : GUI will show IMD Fault fault.

[ System ] : All contactors open.
[ Auto Reset ] : NA.

[ Manual Reset ] : Battery needs to be sent to service center.

|

LMU Temp Open

|

One or more of the slave thermistors might be open. [ GUI ] : GUI will show LMU Temp Open fault.

[ System ] : All contactors open.
[ Auto Reset ] : When the open thermistors are rectified error will be reset after a hard reset.

[ Manual Reset ] : Open thermistors are rectified and a hard reset is done.

|

LMU Temp Short

|

One or more slave thermistors are short. [ GUI ] : GUI will show LMU Temp Short fault.

[ System ] : All contactors open.
[ Auto Reset ] : When the short thermistors are rectified, error will be reset after a hard reset.

[ Manual Reset ] : Short thermistors are rectified and a hard reset is done.

|

LMU Cell Open

|

Cell voltage sensing line is open. [ GUI ] : GUI will show LMU Cell Open fault.

[ System ] : All contactors open.
[ Auto Reset ] : NA.

[ Manual Reset ] : Battery needs to be sent to service center.

|

Fuse Open

|

When contactor close command is given by BMS and pack voltage sense is still below xV. [ GUI ] : GUI will show Fuse Open fault.

[ System ] : All contactors open.
[ Auto Reset ] : Fault will reset when the given condition is untrue.

[ Manual Reset ] : Check pack voltage sense connection or any fuse open in the connection.

|

Precharge Weld

|

Precharge contactor is welded. [ GUI ] : GUI will show Precharge Weld fault.

[ System ] : All contactors open.
[ Auto Reset ] : NA.

[ Manual Reset ] : BMS needs to be sent to service center.

|

Stack Contactor Weld

|

Stack contactor is welded. [ GUI ] : GUI will show Stack Contactor Weld fault.

[ System ] : All contactors open.
[ Auto Reset ] : NA.

[ Manual Reset ] : BMS needs to be sent to service center.

|

Module to Module Contactor Weld

|

Module to Module contactor is welded. [ GUI ] : GUI will show Module to Module Contactor Weld fault.

[ System ] : All contactors open.
[ Auto Reset ] : NA.

[ Manual Reset ] : BMS needs to be sent to service center.

|

Negative Contactor Weld

|

Negative contactor is welded. [ GUI ] : GUI will show Negative Contactor Weld fault.

[ System ] : All contactors open.
[ Auto Reset ] : NA.

[ Manual Reset ] : BMS needs to be sent to service center.

|

Stack Fuse Open

|

When stack contactor close command is given by BMS and load voltage sense is still below xV. [ GUI ] : GUI will show Stack Fuse Open fault.

[ System ] : All contactors open.
[ Auto Reset ] : Fault will reset when the given condition is untrue.

[ Manual Reset ] : Check load voltage sense connection or any fuse open in the connection.

|

Module to Module Fuse Open

|

When stack contactor close command is given by BMS and battery voltage sense is still below xV. [ GUI ] : GUI will show Module to Module Fuse Open fault.

[ System ] : All contactors open.
[ Auto Reset ] : Fault will reset when the given condition is untrue.

[ Manual Reset ] : Check battery voltage sense connection or any fuse open in the connection.